Table 84: Feedback settings
Index Parameter Min Max Unit Default ID Description
P3.13.3.1 Feedback Function 1 9 1 * 333
1 = Only Source1 in use
2 = SQRT(Source1);
(Flow=Constant x
SQRT(Pressure))
3 = SQRT(Source1-
Source 2)
4 = SQRT(Source 1) +
SQRT (Source 2)
5 = Source 1 + Source 2
6 = Source 1 - Source 2
7 = MIN (Source 1,
Source 2)
8 = MAX (Source 1,
Source 2)
9 = MEAN (Source 1,
Source 2)
P3.13.3.2
Feedback Function
Gain
-1000.0 1000.0 % 100.0 1058
Used for example with
the value 2 in Feedback
Function.
PARAMETERS MENU VACON · 177
24-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM