Table 93: Setpoints of the external PID controller
Index Parameter Min Max Unit Default ID Description
P3.14.2.5
Setpoint Source 1
Selection
0 32 1 1643
0 = Not Used
1 = Keypad Setpoint 1
2 = Keypad Setpoint 2
3 = AI1
4 = AI2
5 = AI3
6 = AI4
7 = AI5
8 = AI6
9 =ProcessDataIn1
10 =ProcessDataIn2
11 =ProcessDataIn3
12 =ProcessDataIn4
13 =ProcessDataIn5
14 =ProcessDataIn6
15 =ProcessDataIn7
16 =ProcessDataIn8
17 = Temperature Input
1
18 = Temperature Input
2
19 = Temperature Input
3
20 = Temperature Input
4
21 = Temperature Input
5
22 = Temperature Input
6
23 = Block Out.1
24 = Block Out.2
25 = Block Out.3
26 = Block Out.4
27 = Block Out.5
28 = Block Out.6
29 = Block Out.7
30 = Block Out.8
31 = Block Out.9
32 = Block Out.10
The AIs and the
ProcessDataIn are
handled as percentages
(0.00- 100.00%) and
scaled according to the
setpoint minimum and
maximum.
NOTE!
The ProcessDataIn
signals use 2 decimals.
If you set temperature
inputs, you must set the
setpoint minimum and
maximum scaling
parameters between -50
and 200 °C.