Table 93: Setpoints of the external PID controller
Index Parameter Min Max Unit Default ID Description
P3.14.2.6 Setpoint 1 minimum -200.00 200.00 % 0.00 1644
The minimum value at
the analogue signal
minimum.
P3.14.2.7 Setpoint 1 maximum -200.00 200.00 % 100.00 1645
The maximum value at
the analogue signal
maximum.
P3.14.2.8
Setpoint source 2
selection
0 22 0 1646
See P3.14.2.5.
P3.14.2.9 Setpoint 2 minimum -200.00 200.00 % 0.00 1647
The minimum value at
the analogue signal
minimum.
P3.14.2.10 Setpoint 2 maximum -200.00 200.00 % 100.00 1648
The maximum value at
the analogue signal
maximum.
Table 94: Feedback of the external PID controller
Index Parameter Min Max Unit Default ID Description
P3.14.3.1 Feedback Function 1 9 1 1650
P3.14.3.2
Feedback Function
Gain
-1000.0 1000.0 % 100.0 1651
P3.14.3.3
Feedback 1 Source
Selection
0 25 1 1652
See P3.13.3.3.
P3.14.3.4 Feedback 1 Minimum -200.00 200.00 % 0.00 1653
The minimum value at
the analogue signal
minimum.
P3.14.3.5
Feedback 1
Maximum
-200.00 200.00 % 100.00 1654
The maximum value at
the analogue signal
maximum.
P3.14.3.6
Feedback 2 Source
Selection
0 25 2 1655
See P3.13.3.6.
P3.14.3.7 Feedback 2 Minimum -200.00 200.00 % 0.00 1656
The minimum value at
the analogue signal
minimum.
P3.14.3.8
Feedback 2
Maximum
-200.00 200.00 % 100.00 1657
The maximum value at
the analogue signal
maximum.
PARAMETERS MENU VACON · 191