Selection
number
Selection name Description
0 Binary coded
The mix of the inputs is binary coded. The different sets of
active digital inputs determine the preset frequency. See
more data in the Table Table 117 The selection of preset
frequencies when P3.3.3.1 = Binary coded.
1 Number (of inputs used)
The number of active inputs tells which preset frequency is
used: 1, 2 or 3.
P3.3.3.2 PRESET FREQUENCY 0 (ID 180)
P3.3.3.3 PRESET FREQUENCY 1 (ID 105)
P3.3.3.4 PRESET FREQUENCY 2 (ID 106)
P3.3.3.5 PRESET FREQUENCY 3 (ID 126)
P3.3.3.6 PRESET FREQUENCY 4 (ID 127)
P3.3.3.7 PRESET FREQUENCY 5 (ID 128)
P3.3.3.8 PRESET FREQUENCY 6 (ID 129)
P3.3.3.9 PRESET FREQUENCY 7 (ID 130)
VALUE 0 SELECTED FOR PARAMETER P3.3.3.1:
To set Preset Frequency 0 as reference, set the value 0 Preset Frequency 0 for P3.3.1.5 (I/O
Control Reference A Selection).
To make a selection of a preset frequency between 1 and 7, give digital inputs to P3.3.3.10
(Preset Frequency Selection 0), P3.3.3.11 (Preset Frequency Selection 1), and/or P3.3.3.12
(Preset Frequency Selection 2). The different sets of active digital inputs determine the
preset frequency. You can find more data in the table below. The values of the preset
frequencies stay automatically between the minimum and maximum frequencies (P3.3.1.1
and P3.3.1.2).
Necessary step
Activated frequency
Make a selection of the value 0 for parameter P3.3.1.5. Preset frequency 0
VACON · 244 PARAMETER DESCRIPTIONS