Table 117: The selection of preset frequencies when P3.3.3.1 = Binary coded
Activated digital input signal Activated frequency
reference
Preset Freq Sel2
(P3.3.3.12)
Preset Freq Sel1
(P3.3.3.11)
Preset Freq Sel0
(P3.3.3.10)
Preset frequency 0 Only if
Preset Freq 0 is set as
frequency reference
source with P3.3.3.1.5,
P3.3.1.6, P3.3.1.7 or
P3.3.1.10.
* Preset frequency 1
* Preset frequency 2
* * Preset frequency 3
* Preset frequency 4
* * Preset frequency 5
* * Preset frequency 6
* * * Preset frequency 7
* = the input is activated.
VALUE 1 SELECTED FOR PARAMETER P3.3.3.1:
You can use the Preset Frequencies 1 to 3 with different sets of active digital inputs. The
number of active inputs tells which one is used.
PARAMETER DESCRIPTIONS VACON · 245