ID378
t [s]
Filtered signal
Unfiltered signal
Analogue input
signal
Fig. 46: The AI1 signal filtering
P3.5.2.1.3 AI1 SIGNAL RANGE (ID 379)
To set the type of the analogue input signal (current or voltage), use the dip switches on the
control board. See more in the Installation manual.
It is also possible to use the analogue input signal as frequency reference. The selection of
the value 0 or 1 change the scaling of the analogue input signal.
Selection
number
Selection name Description
0 0...10V / 0...20mA
The range of the analogue input signal is 0...10V or 0...20mA
(the dip switch settings on the control board tell which one).
The input signal is 0...100%.