0 mA 20 mA10 mA
Min freq
reference
Max freq
reference
Frequency
reference
Analogue
input
signal
[Hz]
[%]
Fig. 47: The analogue input signal range, selection 0
Selection
number
Selection name Description
1 2...10V / 4...20mA
The range of the analogue input signal is 2...10V or 4...20mA
(the dip switch settings on the control board tell which one).
The input signal is 20...100%.
0 mA 20 mA10 mA4 mA
Min freq
reference
Max freq
reference
Frequency
reference
Analogue
input
signal
0% 100%50%20%
[Hz]
[%]
Fig. 48: The analogue input signal range, selection 1
P3.5.2.1.4 AI1 CUSTOM. MIN (ID 380)
P3.5.2.1.5 AI1 CUSTOM. MAX (ID 381)
The parameters P3.5.2.1.4 and P3.5.2.1.5 let you adjust the range of the analogue input
signal between -160 and 160% freely.