New starting order of motors
ID428 = TRUE
M1 M2 M4 M5 M3
Fig. 82: The interlock logic 3
When the system stops or goes to sleep mode for the next time, the sequence changes back
to 1, 2, 3, 4, 5.
P3.15.3 INCLUDE FC (ID 1028)
Selection
number
Selection name Description
0 Disabled
The drive is always connected to Motor 1. The interlocks do
not have an effect on Motor 1. Motor 1 is not included in the
autochange logic.
1 Enabled
It is possible to connect the drive to any of the motors in the
system. The interlocks have an effect on all the motors. All
the motors are included in the autochange logic.
WIRING
The connections are different for the parameter values 0 and 1.
SELECTION 0, DISABLED
The drive is directly connected to Motor 1. The other motors are auxiliary motors. They are
connected to the mains by contactors, and controlled by relays of the drive. The autochange
or the interlock logic do not have an effect on Motor 1.