13.3.5.2 Hardware configuration
To be compatible with the Siemens SIMATIC Manager the following steps should be exe-
cuted:
1. Start the Siemens hardware configurator with a new project.
2. Insert a profile rail from the hardware catalog.
3. Place at ‘Slot’ -Number 2 the CPU 314C-2 PN/DP (314-6EH04-0AB0 V3.3).
4. Click at the sub module ‘PN-IO’ of the CPU.
5.
Select ‘Context menu è Insert PROFINET IO System’.
6. Create with [New] a new sub net and assign valid address data.
7. Click at the sub module ‘PN-IO’ of the CPU and open with ‘Context menu
è Properties’ the properties dialog.
8. Enter at ‘General’ a ‘Device name’ . The device name must be unique at the
Ethernet subnet.
Add CPU in the project
VIPA SPEED7
Motion control - Simple Motion Control Library
Usage Sigma-5/7 Pulse Train > Usage in Siemens SIMATIC Manager
HB00 | OPL_SP7 | Operation list | en | 18-30 413