EasyManua.ls Logo

YASKAWA VIPA SPEED7 - Page 414

YASKAWA VIPA SPEED7
1007 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9. Navigate in the hardware catalog to the directory ‘PROFINET IO
è Additional field devices è I/O è VIPA ...’ and connect e.g. for the System
MICRO the IO device ‘M13-CCF0000’ to your PROFINET system.
ð
In the Device overview of the PROFINET IO device ‘VIPA MICRO PLC’ the
CPU is already placed at slot 0.
1. Place for the Ethernet PG/OP channel at slot 4 the Siemens CP 343-1 (SIMATIC
300 \ CP 300 \ Industrial Ethernet \CP 343-1 \ 6GK7 343-1EX30 0XE0 V3.0).
2. Open the properties dialog by clicking on the CP 343-1EX30 and enter for the CP at
‘Properties’ the IP address data. You get valid IP address parameters from your
system administrator.
3. Assign the CP to a ‘Subnet’ . The IP address data are not accepted without assign-
ment!
For parametrization of the input/output periphery and the technological functions the cor-
responding sub modules of the Siemens CPU 314C-2 PN/DP (314-6EH04-0AB0 V3.3) is
to be used. For pulse train output, the sub module count must be switched to ‘Pulse-
width modulation’ . If you are using a channel other than channel 0, you must adapt it in
the hardware configuration and in your user program.
1. Double-click the counter sub module of the CPU 314C-2 PN/DP.
ð
The dialog ‘Properties’ is opened.
2. For example, select ‘channel 0’ and select the function ‘Pulse-width modulation’ as
‘Operating mode’ .
Configuration of Ethernet
PG/OP channel
Switch I/O periphery to
Pulse Train
VIPA SPEED7
Motion control - Simple Motion Control Library
Usage Sigma-5/7 Pulse Train > Usage in Siemens SIMATIC Manager
HB00 | OPL_SP7 | Operation list | en | 18-30 414

Table of Contents

Related product manuals