9. Navigate in the hardware catalog to the directory ‘PROFINET IO
è Additional field devices è I/O è VIPA ...’ and connect e.g. for the System
MICRO the IO device ‘M13-CCF0000’ to your PROFINET system.
ð
In the Device overview of the PROFINET IO device ‘VIPA MICRO PLC’ the
CPU is already placed at slot 0.
1. Place for the Ethernet PG/OP channel at slot 4 the Siemens CP 343-1 (SIMATIC
300 \ CP 300 \ Industrial Ethernet \CP 343-1 \ 6GK7 343-1EX30 0XE0 V3.0).
2. Open the properties dialog by clicking on the CP 343-1EX30 and enter for the CP at
‘Properties’ the IP address data. You get valid IP address parameters from your
system administrator.
3. Assign the CP to a ‘Subnet’ . The IP address data are not accepted without assign-
ment!
For parametrization of the input/output periphery and the technological functions the cor-
responding sub modules of the Siemens CPU 314C-2 PN/DP (314-6EH04-0AB0 V3.3) is
to be used. For PWM output, the sub module count must be switched to ‘Pulse-width
modulation’ . If you are using a channel other than channel 0, you must adapt it in the
hardware configuration and in your user program.
1. Double-click the counter sub module of the CPU 314C-2 PN/DP.
ð
The dialog ‘Properties’ is opened.
2. For example, select ‘channel 0’ and select the function ‘Pulse-width modulation’ as
‘Operating mode’ .
Configuration of Ethernet
PG/OP channel
Switch I/O periphery to
PWM
VIPA SPEED7
Motion control - Simple Motion Control Library
Usage inverter drive via PWM > Usage in Siemens SIMATIC Manager
HB00 | OPL_SP7 | Operation list | en | 18-30 440