EasyManua.ls Logo

YASKAWA VIPA SPEED7 - Page 529

YASKAWA VIPA SPEED7
1007 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11. Navigate in the hardware catalog to the directory ‘PROFINET IO
è Additional field devices è I/O è VIPA SLIO System’ and connect the IO device
‘015-CFFNR00 CPU’ to your PROFINET system.
ð
In the Device overview of the PROFINET IO device ‘VIPA SLIO CPU’ the CPU
is already placed at slot 0. From slot 1 you can place your System SLIO
modules.
1. Place for the Ethernet PG/OP channel at slot 4 the Siemens CP 343-1 (SIMATIC
300 \ CP 300 \ Industrial Ethernet \CP 343-1 \ 6GK7 343-1EX30 0XE0 V3.0).
2. Open the properties dialog by clicking on the CP 343-1EX30 and enter for the CP at
‘Properties’ the IP address data. You get valid IP address parameters from your
system administrator.
3. Assign the CP to a ‘Subnet’ . The IP address data are not accepted without assign-
ment!
1. Navigate in the hardware catalog to the directory ‘PROFINET IO
è Additional field devices è I/O è VIPA EtherCAT System’ and connect the IO
device ‘SLIO EtherCAT System’ to your PROFINET system.
Configuration of Ethernet
PG/OP channel
Insert ‘EtherCAT network’
VIPA SPEED7
Motion control - Simple Motion Control Library
Usage inverter drive via EtherCAT > Usage in Siemens SIMATIC Manager
HB00 | OPL_SP7 | Operation list | en | 18-30 529

Table of Contents

Related product manuals