11. Navigate in the hardware catalog to the directory ‘PROFINET IO
è Additional field devices è I/O è VIPA SLIO System’ and connect the IO device
‘015-CFFNR00 CPU’ to your PROFINET system.
ð
In the Device overview of the PROFINET IO device ‘VIPA SLIO CPU’ the CPU
is already placed at slot 0. From slot 1 you can place your System SLIO
modules.
1. Place for the Ethernet PG/OP channel at slot 4 the Siemens CP 343-1 (SIMATIC
300 \ CP 300 \ Industrial Ethernet \CP 343-1 \ 6GK7 343-1EX30 0XE0 V3.0).
2. Open the properties dialog by clicking on the CP 343-1EX30 and enter for the CP at
‘Properties’ the IP address data. You get valid IP address parameters from your
system administrator.
3. Assign the CP to a ‘Subnet’ . The IP address data are not accepted without assign-
ment!
1. Navigate in the hardware catalog to the directory ‘PROFINET IO
è Additional field devices è I/O è VIPA EtherCAT System’ and connect the IO
device ‘SLIO EtherCAT System’ to your PROFINET system.
Configuration of Ethernet
PG/OP channel
Insert ‘EtherCAT network’
VIPA SPEED7
Motion control - Simple Motion Control Library
Usage inverter drive via EtherCAT > Usage in Siemens SIMATIC Manager
HB00 | OPL_SP7 | Operation list | en | 18-30 529