AINFO PROFINET IO: Data structure of the target area (interrupt information)
Byte Declaration Data type Description
20 ... 23 Submodule ID DWORD Specific information on the source of the interrupt: Submodule ID
24 ... 25 Interrupt speci-
fier
WORD Bits 0 to 10: Sequence number
(range of values: 0 to 2047)
Bit 11: Channel diagnostics:
0: No channel diagnostics available
1: Channel diagnostics available
Bit 12: Status of manufacturer-specific diagnostics:
0: No manufacturer-specific status information available
1: Manufacturer-specific status information available
Bit 13: Status of diagnostics for interface module:
0: No status information available; all errors corrected
1: Diagnostics for at least one channel and/or status information
available
Bit 14: reserved
Bit 15: Application Relationship Diagnosis State
0: None of the configured modules within this AR is reporting a
diagnosis
1: At least one of the configured modules within this AR is reporting
a diagnosis
26 ... 1535 Interrupt speci-
fier
WORD Note:
The additional interrupt specifier can also be omitted.
VIPA SPEED7
Integrated Standard
System Function Blocks > SFB 54 - RALRM - Receiving an interrupt from a periphery module
HB00 | OPL_SP7 | Operation list | en | 18-30 786