STATUS[3] (Error ID) can have the following values:
Error_Decode Error_Code_1 Explanation according to
DP-V1
Description
C1h write constrain conflict The data of the previous write request to
the module for the same record set have
not yet been processed by the module.
C2h resource busy The module currently processes the max-
imum possible jobs for a CPU.
C3h resource unavailable The required operating resources are cur-
rently occupied.
C4h Internal temporary error.
Job could not be carried out. Repeat the
job. If this error occurs often, check your
plant for sources of electrical interference.
C5h DP slave or module not available
C6h Record set transfer was canceled due to
priority class cancellation.
C7h Job canceled due to restart of DP mas-
ters.
C8h ... CFh DP slave or module reports a manufac-
turer specific resource error. Please
check the documentation from the manu-
facturer of the DP slave or module.
Dxh user specific DP slave specific,
81h 00h ... FFh Error in the initial call parameter
(with SFB 54: MODE)
00h Illegal operating mode
82h
...
00h ... FFh Error in the 2. call parameter.
... ...
88h 00h ... FFh Error in the 8. call parameter
(with SFB 54: TINFO)
01h Wrong syntax ID
23h Quantity frame exceeded or target area
too small
24h Wrong range ID
32h DB/DI no. out of user range
3Ah DB/DI no. is zero for area ID DB/DI or
specified DB/DI does not exist.
89h 00h ... FFh Error in the 9. call parameter
(with SFB 54: AINFO)
01h Wrong syntax ID
23h Quantity frame exceeded or target area
too small
24h Wrong range ID
VIPA SPEED7
Integrated Standard
System Function Blocks > SFB 54 - RALRM - Receiving an interrupt from a periphery module
HB00 | OPL_SP7 | Operation list | en | 18-30 793