Parameter Declaration Data Type Description
QLMN_LLM OUTPUT BOOL LOW LIMIT OF MANIPULATED VALUE REACHED
n The value of the manipulated variable is always
limited to an upper and lower limit. The QLMN_LLM
output indicates when the lower limit is exceeded.
n Default: FALSE
QC_ACT OUTPUT BOOL NEXT CYCLE, THE CONTINUOUS CONTROLLER IS
WORKING
n This parameter indicates whether or not the contin-
uous controller stage will be executed at the next
block call (relevant only when SELECT has the
value 0 or 1).
n Default: TRUE
CYCLE INPUT/ OUTPUT REAL SAMPLE TIME OF CONTINUOUS CONTROLLER [s]
n This sets the sampling time for the PID algorithm.
The tuner calculates the sampling time in Phase 1
and enters this in CYCLE.
n Default: 0.1s
n Range of Values: ³ 1ms
CYCLE_P INPUT/ OUTPUT REAL SAMPLE TIME OF PULSE GENERATOR [s]
n At this input, you enter the sampling time for the
pulse generator stage. FB 58 "TCONT_CP" calcu-
lates the sampling time in Phase 1 and enters it in
CYCLE_P.
n Default: 0.2s
n Range of Values: ³ 1ms
SP_INT INPUT/ OUTPUT REAL INTERNAL SETPOINT
n The SP_INT input is used to specify a setpoint.
n Default: 0.0
n Range of Values: Value range of the process value
MAN INPUT/ OUTPUT REAL MANUAL VALUE
n The MAN input is used to specify a manual value.
In automatic mode, it is corrected to the manipu-
lated variable.
n Default: 0.0
COM_RST INPUT/ OUTPUT REAL COMPLETE RESTART
n The block has an initialization routine that is pro-
cessed when the COM_RST input is set.
n Default: FALSE
MAN_ON INPUT/ OUTPUT REAL MANUAL OPERATION ON
n If the MAN_ON input is set, the control loop is inter-
rupted. The MAN manual value is set as the value
of the manipulated variable.
n Default: TRUE
VIPA SPEED7
Standard
PID Control > FB 58 - TCONT_CP - Continuous Temperature Control
HB00 | OPL_SP7 | Operation list | en | 18-30 856