Internal Parameters
Parameter Declaration Data type Description
DEADB_W INPUT REAL DEAD BAND WIDTH
n The error passes through a dead band. The
DEADB_W input decides the size of the dead
band.
n Default: 0.0
n Range of Values: Dependent on the sensors used
I_ITLVAL INPUT REAL INITIALIZATION VALUE OF THE INTEGRAL ACTION
n The output of the integral action can be set at the
I_ITL_ON input. The initialization value is applied to
the I_ITLVAL input.
n During a restart COM_RST = TRUE, the I action is
set to the initialization value.
n Default: 0.0
n Range of Values: 0 to 100 %
LMN_HLM INPUT REAL MANIPULATED VARIABLE HIGH LIMIT
n The value of the manipulated variable is always
limited to an upper and lower limit. The LMN_HLM
input specifies the upper limit.
n Default: 100.0
n Range of Values: > LMN_ LLM
LMN_LLM INPUT REAL MANIPULATED VARIABLE LOW LIMIT
n The value of the manipulated variable is always
limited to an upper and lower limit. The LMN_LLM
input specifies the lower limit.
n Default: 0.0
n Range of Values: < LMN_HLM
PV_FAC INPUT REAL PROCESS VARIABLE FACTOR
n The PV_FAC input is multiplied by the PV_PER.
The input is used to adapt the process variable
range.
n Default: 1.0
PV_OFFS INPUT REAL PROCESS VARIABLE OFFSET
n The PV_OFFS input is added to the PV_PER. The
input is used to adapt the process variable range.
n Default: 0.0
LMN_FAC INPUT REAL MANIPULATED VARIABLE FACTOR
n The LMN_FAC input is multiplied by the manipu-
lated variable. The input is used to adapt the
manipulated variable range.
n Default: 1.0
LMN_OFFS INPUT REAL MANIPULATED VARIABLE OFFSET
n The LMN_OFFS input is added to the value of the
manipulated variable. The input is used to adapt
the manipulated variable range.
n Default: 0.0