Parameter Declaration Data type Description
PER_TM INPUT REAL PERIOD TIME [s]
n The pulse repetition period of the pulse duration
modulation is entered at the PER_TM parameter.
The relationship of the pulse repetition period to the
sampling time of the pulse generator decides the
accuracy of the pulse duration modulation.
n Default: 1.0 s
n Range of Values: ³ CYCLE
P_B_TM INPUT REAL MINIMUM PULSE/BREAK TIME [s]
n A minimum pulse or minimum break time can be
set at the P_B_TM parameter. P_B_TM is limited
internally to > CYCLE_P.
n Default: 0.02 s
n Range of Values: ³ 0.0
TUN_DLMN INPUT REAL DELTA MANIPULATED VARIABLE FOR PROCESS
EXCITATION
n Process excitation for controller tuning results from
a setpoint step change at TUN_DLMN.
n Default: 20.0
n Range of Values: -100.0 ... 100.0 %
PER_MODE INPUT INT PERIPHERY MODE
n You can enter the type of the I/O module at this
switch. The process variable at input PV_PER is
then normalized to °C at the PV output.
– PER_MODE = 0: standard
– PER_MODE = 1: climate
– PER_MODE = 2: current/voltage
n Default: 0
n Range of Values: 0, 1, 2
PVPER_ON INPUT BOOL PROCESS VARIABLE PERIPHERY ON
n If you want the process variable to be read in from
the I/O, the PV_PER input must be connected to
the I/O and the PVPER_ON input must be set.
n Default: FALSE
I_ITL_ON INPUT BOOL INITIALIZATION OF THE INTEGRAL ACTION ON
n The output of the integral action can be set to the
I_ITLVAL input. The I_ITL_ON input must be set.
n Default: FALSE
PULSE_ON INPUT BOOL PULSE GENERATOR ON
n If PULSE_ON = TRUE is set, the pulse generator is
activated
n Default: FALSE
TUN_KEEP INPUT BOOL KEEP TUNING ON
n The mode changes to automatic only when
TUN_KEEP changes to FALSE.
n Default: FALSE
VIPA SPEED7
Standard
PID Control > FB 58 - TCONT_CP - Continuous Temperature Control
HB00 | OPL_SP7 | Operation list | en | 18-30 858