EasyManua.ls Logo

Agilent Technologies 8753ET - Source

Agilent Technologies 8753ET
617 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-14 Chapter 4
Start Troubleshooting Here
Source
Source
Phase Lock Error Messages
The error messages listed below are usually indicative of a source failure or improper
instrument configuration. (Ensure that the R channel input is receiving at least 35 dBm
power). Continue with this procedure.
NO IF FOUND: CHECK R INPUT LEVEL
The first IF was not detected during the pretune stage of phase lock.
NO PHASE LOCK: CHECK R INPUT LEVEL
The first IF was detected at the pretune stage but phase lock could not be acquired
thereafter.
PHASE LOCK LOST
Phase lock was acquired but then lost.
PHASE LOCK CAL FAILED
An internal phase lock calibration routine is automatically executed at power-on, when
pretune values drift, or when phase lock problems are detected. A problem spoiled a
calibration attempt.
POSSIBLE FALSE LOCK
The analyzer is achieving phase lock but possibly on the wrong harmonic comb tooth.
SWEEP TIME TOO FAST
The fractional-N and the digital IF circuits have lost synchronization.
Check Source Output Power
1. Connect the equipment as shown in Figure 4-5. Be sure that any special accessories,
such as limiters, have been disconnected.

Table of Contents

Other manuals for Agilent Technologies 8753ET

Related product manuals