148
Auxiliary functions
3.
ADD.DIAGNOSE
– Activation and deactivation of diagnosis functions
Diagnosis functions can be activated in this menu and incorporated into the DIAGNOSE main menu or already
activated diagnosis functions can be deactivated again.
Activation of diagnosis functions:
For description see Chapter “26.2.22.4. Activation of diagnosis functions”
Deactivation of diagnosis functions:
The procedure is the same as for activation. Except that with deactivation the cross after the diagnosis function is
removed again by pressing the
ENTER
key .
4.
RESET.HISTORY
– Deletion of the history entries of all diagnosis functions
Explanation of the history entries:
There is a history entry for each diagnosis message. This entry is assigned to the diagnosis function, which has
actuated this message, and is saved there in the HISTORY submenu.
In the menu of some diagnosis functions there is a HISTORY submenu in which the history entries are
saved.
RESET.HISTORY is used to delete the entries of all HISTORY submenus.
Individual entries can be deleted in the HISTORY submenu of the particular diagnosis function.
See also chapter “26.2.22.7. History entries in the HISTORY submenu”.
Deleting all history entries:
Key Action Description
/ Select RESET.HISTORY
RUN
Hold down
as long as countdown (5 ...) is
running
All history entries are deleted.
EXIT
Press
Return to the DIAGNOSE main menu.
Table 82: RESET.HISTORY; deleting all history entries
CAUTION!
History entries are only created when the CLOCK function for the display has been activated on the
process level.