EasyManua.ls Logo

Fujitsu ETERNUS CS800 S5 - Installing the Rack; Rack Requirements

Fujitsu ETERNUS CS800 S5
634 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
U41840-J-Z125-7-76 81
Installing the Rack
I
It is recommended to install the ETERNUS CS800 S5 system in a controlled or
restricted area to prevent access by untrained personnel. In addition, it is
recommended that system installation is performed only by qualified IT personnel.
Rack Requirements
Table 18 and Table 19 contain the rack requirements for the ETERNUS CS800 S5 compo-
nents.
Table 18: Rack Requirements - for Entry
Table 19: Rack Requirements - for Scale
The rack systems from Fujitsu (PRIMECENTER Rack) support the installation of
ETERNUS CS800 S5 components. Installation in most current rack systems from other
manufacturers is also supported.
To ensure proper ventilation, any unused areas in the rack must be sealed using dummy
covers. Ventilation takes place from the front to the back and may not be obstructed!
The power is supplied via the multiple socket outlets fitted in the rack.
ETERNUS CS800 S5 - Entry
With JX40 storage modules
Height 2 HU, i.e. 8.9 cm, 4 HU, i.e. 17.8 cm
Width (side to side) 48.26 cm 48.26 cm
Depth (front to back) 77 cm 77 cm
Weight (stand alone) 25 kg 60 kg
Ventilation Clearance At least 200 mm on the front and rear
ETERNUS CS800 S5 - Scale
With DX80 S2 expansion modules
Height 4 HU, i.e. 17.8 cm Up to 22 HU, i.e. 97.8 cm (9 expansions)
Width (side to side) 48.26 cm 48.26 cm
Depth (front to back) 77 cm 77 cm
Weight (stand alone) 60 kg Up to 375 kg
Ventilation Clearance At least 200 mm on the front and rear

Table of Contents

Related product manuals