POSSIBLE MALFUNCTIONS AND TROUBLESHOOTING 
Information for general use 
Rev. M / 73023639 
 
9.2.  List of possible errors 
These  are  alarms,  warnings,  messages or  hints  which  are  generated  by  different  software  parts 
(called AFB or SFB). All events are binary. They may or may not exist at a certain point in time.  
Often the reason for the display is already mentioned in the message text. e.g. archive entries lost.  
A current list of all possible display texts of the device can be found in the export value window of 
enSuite under the respective AFB's or SFB's  8 Configuration and analysis software enSuite 
 
Many warning and alarm messages can be prevent or eliminate by changing the 
parameterizationsee 
8.4 Changing existing device settings (Parameterization) 
If the parameterization does not show any errors, please contact Honeywell. 
 
The following section provides a summarized selection of event-related display texts of the device. 
Depending on the software version, the message text may differ from the examples shown here, but 
the meaning of the message is not changed. 
 
Cause of Time Service SFB messages  
The system time is further away from the external time than 
permitted. Only the synchronization is permitted, not the 
adjustment of the system time.  
The system time should be adjusted since it deviates from the 
external time more than permitted. However, only synchro-
nization, not the adjustment of the system time, is permitted.  
 Alarm or   Warning 
ext. time source  
External time sources are used and are marked as erroneous, 
a warning or alarm is parameterized.  
 Daylight saving: manual. 
Configuration invalid.  
Time switchover (daylight saving time) not completed.  
The cause depends on the selected mode for daylight saving 
time switchover. 
Cause of System SFB messages  
If an “approval file” is used, the parameter set is monitored by 
the checksum (CRC).  
In the event of discrepancies due to unauthorized changes, 
the appropriate alarm or warning is triggered.