↓ Go to step 10.
9. Perform the following
a. See “Chapter 5. Locations, Addresses, and Part Listings” on page 705 to
determine the location of AC module A01.
b. Trace the AC input line cord that connects to AC module A01.
Attention: Do not disconnect the other system line cord when powered
on.
c. Go to step 12.
10. Is the SRC 1xxx-02AC?
Yes No
↓ Go to step 16 on page 399.
11. Perform the following:
a. See “Chapter 5. Locations, Addresses, and Part Listings” on page 705 to
determine the location of AC module A03.
b. Trace the AC input line cord that connects to AC module A03.
Attention: Do not disconnect the other system line cord when powered
on.
c. Go to step 12.
12. Perform the following:
a. Disconnect the mainline AC power cable (1) from the AC module for the
SRC you are working on.
b. Use a multimeter to measure the AC voltage at the AC module end of the
mainline AC power cable.
13. Is the AC voltage from 200 V AC to 240 V AC?
No Yes
↓ Exchange the failing AC module 1 for SRC 01AC or AC module 2 for
02AC:
v USA – part 21H7000
v World Trade 1PH – part 21H7261
This ends the procedure.
14. Perform the following:
a. Disconnect the mainline AC power cable from the customer’s AC power
outlet.
b. Use a multimeter to measure the AC voltage at the customer’s AC power
outlet.
Is the AC voltage from 200 V AC to 240 V AC?
Yes No
↓ Perform the following:
a. Inform the customer that the AC voltage at the power outlet is not
correct.
b. Reconnect the mainline AC power cables to the power outlet.
This ends the procedure.
15. Exchange the failing mainline AC power cable.
This ends the procedure.
Power PIPs
398
iSeries Model 830, 840, SB2, and SB3 Problem Analysis, Repair and Parts V5R1