EasyManua.ls Logo

Juniper SRX5400 - Page 410

Juniper SRX5400
438 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The marked input voltage of -48 VDC for a DC-powered services gateway is the nominal voltage
associated with the battery circuit, and any higher voltages are only to be associated with float voltages
for the charging function.
Because the services gateway is a positive ground system, you must connect the positive lead to the
terminal labeled RETURN, the negative lead to the terminal labeled -48V, and the earth ground to the
chassis grounding points.
416

Table of Contents

Other manuals for Juniper SRX5400

Related product manuals