Keyscan Technical Guide (PC109x - 04.12)
155
Table 30 – WIEEX2/CWIEEX2 Cables and Distances
Unit Connections Maximum Distance Cable
WIEEX2 Transmitter (Tx) to Reader 500 feet (152.4 m) Refer to Table 1 – Cable Requirements - Readers
WIEEX2 Transmitter (Tx) to Receiver
(Rx)
4000 feet (1219.2 m) CAT 5 - 1 twisted pair (communication)
1 pair 18AWG power if no local independent power
supply
WIEEX2 Receiver (Rx) to ACU 500 feet (152.4 m)
CWIEEX2 Transmitter (Tx) to Reader 500 feet (152.4 m) Refer to Table 1 – Cable Requirements – Readers
CWIEEX2 Transmitter (Tx) to Receiver
(Rx)
500 feet (152.4 m) RG59U
CWIEEX2 Receiver (Rx) to ACU 500 feet (152.4 m)
WIEEX2 (RS485) - Installation Notes
Existing 22 AWG UTP can be used between a WIEEX2 transmitter and receiver provided it is in good condition
without breaks or high impedance splices. Nominal resistance for 22 AWG UTP is approximately 18 ohms/1000
feet.
Short J1 on the WIEEX2 transmitter and receiver.
Connect the WIEEX2 transmitter (Tx) to the reader, door contact, request to exit device, auxiliary input, and
door lock, whichever are applicable.
Connect the WIEEX2 receiver (Rx) to the appropriate ACU terminals.
Power the transmitter with a 12VDC 1Amp power supply, if a local power supply is required and not sourced
from the ACU.
The Door Unlock Output (RA2/OC) is defaulted for 'fail safe'. If 'fail secure' is required on a WIEEX2 (firmware
6.00 or higher), connect RB4 on the receiver to the ‘normally closed’ position on the ACU lock relay.
The WIEEX2 transmitter (Tx) can control a lock device or relay to a maximum of 12 VDC, 500 mA.
CWIEEX2 (COAX) - Installation Notes
Existing coaxial cable can be used between a CWIEEX2 transmitter and receiver provided it is in good condition
without breaks or high impedance splices.
Connect the CWIEEX2 transmitter (Tx) to the reader, door contact, request to exit device, auxiliary input, and
door lock, whichever are applicable.
Connect the CWIEEX2 receiver (Rx) to the appropriate ACU terminals.
The Door Unlock Output (RA2/OC) is defaulted for 'fail safe'. If 'fail secure' is required on a CWIEEX2 (firmware
6.00 or higher), connect RB4 on the receiver to the ‘normally closed’ position on the ACU lock relay.
The CWIEEX2 transmitter (Tx) can control a lock device or relay to a maximum of 12 VDC, 500 mA.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Keyscan EC2500 Series and is the answer not in the manual?

Keyscan EC2500 Series Specifications

General IconGeneral
BrandKeyscan
ModelEC2500 Series
CategoryControl Unit
LanguageEnglish

Related product manuals