EasyManua.ls Logo

Keyscan EC2500 Series - Page 41

Default Icon
200 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Keyscan Technical Guide (PC109x - 04.12)
38
Terminate Input Wiring
The following sub-headings review termination of door, exit, and auxiliary alarm input wiring.
Door Monitoring Connections
A normally-closed door contact is for monitoring door security. Door inputs are shunted during the door relay
unlock time.
Exit Device Connections
A normally-open exit device contact unlocks its assigned door for its defined door relay unlock time and
overrides the alarm input during its defined door held open time. Examples of exit devices are exit push
buttons or motion sensors (PIR) etc.
Keyscan recommends a PIR with a pulse output of 1/2 second and suited to its environment.
Security Monitoring Connections
A normally-closed device may be connected to an auxiliary alarm input for monitoring stairwell or interior
doors, or windows. The auxiliary alarm inputs may be connected to infrared sensors or to an existing alarm
system with a normally-closed auxiliary output relay contact.

Table of Contents

Related product manuals