190
No.
Communi-
cation
Address
LCD Display
Name
Setting Range
Initial
Value
Shift in
Opera-
tion
Control Mode
V
/
F
S
L
V
C
S
L
T
V
C
T
27
0h1A1B
Stop Freq 1
1st auxiliary motor
stop frequency
0
60 (Hz)
15.00
O
O
O
O
X
X
28
0h1A1C
Stop Freq 2
2nd auxiliary motor
stop frequency
0
60 (Hz)
15.00
O
O
O
O
X
X
29
0h1A1D
Stop Freq 3
3rd auxiliary motor
stop frequency
0
60 (Hz)
15.00
O
O
O
O
X
X
30
0h1A1E
Stop Freq 4
4th auxiliary motor
stop frequency
0
60 (Hz)
15.00
O
O
O
O
X
X
31
0h1A1F
Aux Start DT
Auxiliary motor
starting delay time
0
3600.0 (sec)
60.0
O
O
O
O
X
X
32
0h1A20
Aux Stop DT
Auxiliary motor stop
delay time
0
3600.0 (sec)
60.0
O
O
O
O
X
X
33
0h1A21
Num of Aux
Auxiliary motor
number selection
0
4
4
X
O
O
O
X
X
34
0h1A22
Regul Bypass
Bypass selection
0
No
0:No
X
O
O
O
X
X
1
Yes
35
0h1A23
Auto Ch Mode
Auto change mode
selection
0
None
1: Aux
X
O
O
O
X
X
1
Aux
2
Main
36
0h1A24
Auto Ch Time
Auto change time
0
99:00 (min)
72:00
O
O
O
O
X
X
38
0h1A26
Interlock
Interlock selection
0
No
0:No
O
O
O
O
X
X
1
Yes
39
0h1A27
Interlock DT
Interlock movement
delay time
0.1
360.0
(sec)
5.0
O
O
O
O
X
X
40
0h1A28
Actual Pr Diff
Auxiliary motor
movement pressure
difference
0
100 (%)
2
O
O
O
O
X
X
41
0h1A29
Aux Acc Time
Main motor
acceleration time
when number of
pumps decreases
0
600.0 (sec)
2.0
O
O
O
O
X
X
42
0h1A2A
Aux Dec Time
Main motor
deceleration time
when number of
pumps increases
0
600.0 (sec)
2.0
O
O
O
O
X
X
58
Note
39
)
0h1A3A
PLC LED
Status
PLC option LED status
-
-
O
O
O
O
O
O
59
0h1A3B
PLC S/W Ver
PLC option module
S/W version
-
1.X
O
O
O
O
O
O
60
0h1A3C
PLC Wr Data 1
PLC write data 1
0
FFFF (Hex)
0000
O
O
O
O
O
O
61
0h1A3D
PLC Wr Data 2
PLC write data 2
0
FFFF (Hex)
0000
O
O
O
O
O
O
62
0h1A3E
PLC Wr Data 3
PLC write data 3
0
FFFF (Hex)
0000
O
O
O
O
O
O
63
0h1A3F
PLC Wr Data 4
PLC write data 4
0
FFFF (Hex)
0000
O
O
O
O
O
O
64
0h1A40
PLC Wr Data 5
PLC write data 5
0
FFFF (Hex)
0000
O
O
O
O
O
O
65
0h1A41
PLC Wr Data 6
PLC write data 6
0
FFFF (Hex)
0000
O
O
O