EasyManuals Logo

LSIS SV-IS7 User Manual

LSIS SV-IS7
255 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #205 background imageLoading...
Page #205 background image
194
No.
Communi
-cation
Address
LCD Display
Name
Setting Range
Initial
Value
Shift in
Opera-
tion
Control Mode
V
/
F
S
L
V
C
S
L
T
V
C
T
50
0h1B32
Stall Prevent
Stall prevention
Bit
0000
1111
0000
X
O
O
X
O
X
1
Accelerating
2
Steady speed
3
Decelerating
4
Flux Breaking
51
0h1B33
Stall Freq 1
Stall frequency 1
Start frequency
-stall frequency 1 (Hz)
60.00
O
O
O
X
O
X
52
0h1B34
Stall Level 1
Stall level 1
30
250 (%)
180
X
O
O
X
O
X
53
0h1B35
Stall Freq 2
Stall frequency 2
Stall frequency 1
stall frequency 2 (Hz)
60.00
O
O
O
X
O
X
54
0h1B36
Stall Level 2
Stall level 2
30
250 (%)
180
X
O
O
X
O
X
55
0h1B37
Stall Freq 3
Stall frequency 3
Stall frequency 2
stall frequency 4 (Hz)
60.00
O
O
O
X
O
X
56
0h1B38
Stall Level 3
Stall level 3
30
250 (%)
180
X
O
O
X
O
X
57
0h1B39
Stall Freq 4
Stall frequency 4
Stall frequency 3
maximum frequency
(Hz)
60.00
O
O
O
X
O
X
58
0h1B3A
Stall Level 4
Stall level 4
30
250 (%)
180
X
O
O
X
O
X
66
0h1B42
DB
Warn %ED
DB resistance warning level
0
30 (%)
0
O
O
O
O
O
O
70
0h1B46
Over SPD
Freq
Overspeed decision
frequency
20
130 (%)
120.0
O
X
X
O
X
O
72
0h1B48
Over SPD
Time
Overspeed judgment time
0.01
10.00 (sec)
0.01
O
X
X
O
X
O
73
0h1B49
Speed Dev
Trip
Speed error failure
0
No
0:No
O
X
X
O
X
X
1
Yes
74
0h1B4A
Speed Dev
Band
Speed error width
2-maximum
frequency (Hz)
20.00
O
X
X
O
X
X
75
0h1B4B
Speed Dev
Time
Speed error judgment
time
0.1
1000.0 (sec)
1.0
O
X
X
O
X
X
77
0h1B4D
Enc Wire
Check
Encoder option connection
check
0
No
0:No
O
X
X
O
X
O
1
Yes
78
0h1B4E
Enc Check
Time
Encoder connection check
time
0.1
1000.0 (sec)
1.0
O
X
X
O
X
O
79
0h1B4F
FAN Trip
Mode
Cooling fan fault selection
0
Trip
1:
Warning
O
O
O
O
O
O
1
Warning
80
0h1B50
Opt Trip
Mode
Operation selection on
optional module trip
0
None
1:Free-
Run
O
O
O
O
O
O
1
Free-Run
2
Dec
81
0h1B51
LVT Delay
Low voltage trip
decision delay time
0
60.0 (sec)
0.0
X
O
O
O
O
O
82
0h1B52
LV2 Enable
Select Low Voltage2 during
operation
0
No
0:No
X
O
O
O
O
O
1
Yes
* The grey cells indicate a hidden code which is only visible when setting a code.
Note 40)
PRT-10 codes are displayed only when PRT-09(Retry Number) is set above0.
Note 41)
PRT-13
15 codes are displayed only when PRT-12(Lost Cmd Mode) is not “None”.
Note 42)
PRT-32
33 codes are displayed only when PRT-31(No Motor Trip is set as “Free-Run”.