EasyManua.ls Logo

Mack ASET AC - VTG Actuating System Calibration

Default Icon
536 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
REPAIR INSTRUCTIONS, PART 2
Page 435
VTG Actuating System Calibration
The VTG actuating system must be recalibrated
for proper open and closed vane position
voltages and full stop-to-stop travel whenever
parts are replaced, or when diagnosing certain
conditions (such as an active 4-5 fault code).
Recalibrate the VTG actuating system during any
of the following circumstances:
Turbocharger replacement
VTG actuator replacement
Actuator control valve replacement
Active code 4-5, MID 128, PID269, FMI7
(Refer to the V-MAC
®
III Service Manual,
8-311.)
Complaints of low power or low boost
pressure
VTG CALIBRATION TEST
To perform the VTG calibration test, use
V-MAC
®
III Support Software, Service
Diagnostics. The VTG calibration test is located
within Special Diagnostic Modes, VTG Vane
Position Calibration.
When performing the VTG Vane Position
Calibration test, engine coolant temperature must
be above 140°F (60°C), engine not running, and
the key switch in the ON position. Air system
pressure (both primary and secondary) must be
at least 110 psi. Air system pressure at 110 psi is
mandatory to ensure that at all times during the
calibration procedures, the vane actuator
receives a minimum of 95 psi. This pressure is
required for the vanes to reach full travel.
If the turbocharger is too hot to touch, the engine
should be run at an idle, then allowed to cool
before the calibration procedure is performed.
During the calibration test, the actuator rod must
be observed to ensure that full rod travel takes
place, and that the vane operating lever reaches
both the upper and lower stops. If the actuator
does not visibly reach the full stop positions, the
test results have failed, even if the diagnostic tool
reports a successful test. If the actuator did not
reach the full stop positions, either air system
pressure was too low, or there was a mechanical
problem with the vane operating lever, actuator,
control valve, etc., that must be resolved. Verify
that air system pressure is at least 110 psi (95 psi
delivered to the actuator), and check the actuator
and vanes for proper function as outlined under
the heading “Checking Actuator and Vane
Function.
CALIBRATING ACTUATOR ROD TRAVEL
If the calibration test results indicated that
adjustment of actuator rod travel is necessary,
adjust the rod as follows:
1. Loosen the actuator rod end jam nut while
holding the rod end with an open-end
wrench to prevent the actuator rod from
twisting.
2. Disconnect the air line from the 90-degree
fitting at the top of the actuator.
3. Connect a regulated shop air supply (with a
pressure gauge) to the actuator, and apply
40–60 psi. Be careful not to apply pressure
greater than 100 psi, as damage to the
actuator will result.
533
Figure 533 — Regulated Shop Air Connected to Actuator
1. Regulated Shop Air
Supply Line
2. Vane Actuator
5-111.bk Page 435 Monday, July 10, 2006 2:26 PM

Table of Contents

Related product manuals