7 Function Code Table
- 183 -
Function
Code
Parameter Name Setting Range Default Unit Property Page
Group FC: Protection function parameters
FC-00
Program control for
protection function
Bit0: Short circuit to ground
detection at power-on
Bit2: Decelerating to stop at valid
light curtain
Bit9: Mode without door open/
close limit
Bit10: Light-load input
0 -
★
246
FC-01
Program control 2 for
protection function
Bit0: Overload protection
Bit1: Canceling protection at
output phase loss
Bit2: Canceling over-modulation
function
Bit4: Light curtain judgment at
door close limit
Bit5: Canceling SPI
communication judgment
Bit14: Canceling protection at
input phase loss
65 -
★
246
FC-02
Overload protection
coefcient
0.50–10.00 1.00 -
★
246
FC-03
Overload pre-warning
coefcient
50–100 80 %
★
246
FC-04
Opposite door
selection
0: Simultaneous control
1: Hall call independent, car call
simultaneous
2: Hall call independent, car call
manual control
3: Hall call independent, car call
independent
0 -
★
246
FC-06 Designated fault 0–99 0 -
☆
244
FC-07 Designated fault code 0–9999 0 -
●
247
FC-08
Designated fault
subcode
0–65535 0 -
●
247
FC-09
Designated fault
month and day
0–1231 0 MM.DD
●
247
FC-10
Designated fault hour
and minute
0–23.59 0 HH.MM
●
247
FC-11
Logic information of
designated fault
0–65535 0 -
●
247
FC-12
Curve information of
designated fault
0–65535 0 -
●
247
FC-13
Set speed upon
designated fault
0.000–4.000 0 m/s
●
247
FC-14
Feedback speed upon
designated fault
0.000–4.000 0 m/s
●
247