8.10 Elevator Commissioning Parameters
Before performing elevator commissioning, check whether the shaft is unobstructed and all related
parameters are set correctly.
First run the elevator at inspection speed to the middle oor to ensure correct running direction. Run a
single oor call, and then run multiple oor calls.
After the commissioning is completed, check whether the parameters in this section are set properly.
8.10.1 Car Call and Hall Call Test
Function Code Parameter Name Setting Range Default
Unit Property
F7-00
Car call oor registered 0 to F6-00 0
-
☆
F7-01
Up call oor registered 0 to F6-00 0
-
☆
F7-02
Down call oor registered 0 to F6-00 0
-
☆
These parameters are used to set the destination oors at elevator commissioning or repairing. They can
be respectively used as the car call button, hall call up button and hall call down button. They remain valid
after the commissioning command is input, and become invalid until they are set to 0 or the system suffers
power failure.
8.10.2 Random Running Test
Function Code Parameter Name Setting Range Default Unit Property
F7-03
Random running times 0–60000 0
-
☆
F7-08
Time interval of random running 0–1000 0 s
☆
The NICE3000
new
has the random automatic running function. If the setting of F7-03 is greater than 60000,
the system keeps implementing random automatic running until you set F7-03 to 0.
You can set the time interval between two times of random running in F7-08.
8.10.3 Hall Call, Door Open, Overload, and Limit Enable
Function Code Parameter Name Setting Range Default Unit Property
F7-04
Hall call forbidden
0: No
1: Yes
0 -
☆
F7-05
Door open forbidden
0: No
1: Yes
0 -
☆
F7-06
Overload function
0: Disabled
1: Enabled
0 -
☆
F7-07
Limit switch forbidden
0: No
1: Yes
0 -
☆
●
F7-04 is used to forbid the hall calls.
0: No (hall call allowed)