NICE3000
new
User Manual 8 Description of Function Codes
- 223 -
Bit Function Description Default
Bit14
Opening door by holding
down the door open button
In the re emergency state, the door open process can be
completed only by holding down the door open button until
the door open limit is reached. Otherwise, it will be switched
over to door close automatically.
0
Bit15
Automatic door open at re
emergency oor
The door opens automatically after the elevator arrives at
the re emergency oor.
0
8.9.2 Security Floor Function
Function Code Parameter Name Setting Range Default Unit Property
FE-32
Elevator function selection 1
Bit5: Night security oor
function
0 -
☆
F6-13
Security oor 0 to F6-00 0 -
★
Fd-07
HCB:JP1 input
5/37: Security oor signal
0 -
★
Fd-08
HCB:JP2 input 0 -
★
F6-13 is used to set the security oor of the elevator. If the security signal is active or it is during the night
security period, the elevator runs to the security oor rst every time, opens and closes the door once, and
then runs to the target oor.
The elevator can be made to stop at the security oor in the following two ways:
●
Fd-07/Fd-08 is set to 5/37 (Security signal). If the security signal is active, the elevator enters the
security state.
●
The night security oor function is enabled (FE-32 Bit5 = 2), the elevator enters the security state
from 22:00 p.m. to 6:00 a.m.
8.9.3 Elevator Lock Function
Function Code Parameter Name Setting Range Default Unit Property
F6-04
Elevator lock oor F6-01 to F6-00 1 -
★
F6-40
Program control selection 1 Bit5: Timed elevator lock 0 -
★
F6-38
Elevator lock start time 00.00–23.59 00.00 HH.MM
☆
F6-39
Elevator lock end time 00.00–23.59 00.00 HH.MM
☆
Fd-07
HCB: JP1 input 1/33: Elevator lock signal 1 -
★
F6-04 is used to set the elevator lock oor. In the automatic running state, if the elevator lock switch
is turned on or the set elevator lock time is reached, the elevator cancels all registered hall calls and
responds to all registered car calls, returns to the elevator lock oor, stops automatic running, and closes
the lamp and fan in the car; after the door closes, the elevator cancels hall call display.
The elevator can switch to the locked state in the following two ways:
●
F6-40 Bit5 = 1, to enable the timed elevator lock function.
F6-38 and F6-39 are used to set the elevator lock time period, during which the elevator is in
locked state.
●
Fd-07 = 1/33, to enable the hall elevator lock switch