8 Description of Function Codes NICE3000
new
User Manual
- 252 -
8.18.2 Floor Special Display Setting
Function Code Parameter Name Setting Range Default Unit Property
FE-52
Highest digit selection 1
0–4099
0 -
☆
FE-53
Highest digit selection 2 0 -
☆
FE-54
Highest digit selection 3 0 -
☆
FE-55
Highest digit selection 4 0 -
☆
FE-56
Highest digit selection 5 0 -
☆
When the 2-digit display cannot meet the requirement, you can add the third-digit display by setting these
parameters as follows:
Step 1: Set the two high digits for indicating the oor address that requires special display, and set the two
low digits for indicating the display content.
For example, if oor 18 needs to be displayed as "17A", set FE-18 to 0710 (displaying "7A") and then set
the FE-52 to 1801 (displaying "1").
Figure 8-30 Setting oor 18 display to "17A"
FE-52 = 1801
FE-18 (Floor 18 display)
= 0710
01
Floor address for
special display ("18")
Special display
content ("1")
18 10
Display "7" Display "A"
07
1
7A
Floor 18 display
Step 2: Set F8-14 Bit0 to 1.
Step 3: Power off the system and power it on again.
8.19 Leveling Adjustment
Function Code Parameter Name Setting Range Default Unit Property
F4-00
Leveling adjustment 0–60 30 mm
★
Fr-00
Leveling adjustment function
0: Disabled
1: Enabled
0 -
★
Fr-01
Leveling adjustment record 1
00000–60060
30030 mm
★
Fr-02
Leveling adjustment record 2 30030 mm
★
…
…
Fr-20
Leveling adjustment record 20 30030 mm
★
●
F4-00 is used to adjust the leveling accuracy at elevator stop.
If over-leveling occurs at all oors during elevator stop, decrease the value of this parameter
properly. If under-leveling occurs at all oors during elevator stop, increase the value of this
parameter properly.