8 Description of Function Codes NICE3000
new
User Manual
- 246 -
8.14.5 Special Door Open, Manual Holding, and Forced Door Close Time
Function Code Parameter Name Setting Range Default Unit
Property
Fb-15
Special door open holding time 10–1000 30 s
☆
Fb-16
Manual door open holding time 1–60 5 s
☆
Fb-17
Holding time for forced door close 5–180 120 s
☆
●
FB-15 is used to set the door open holding time when there is a disability call.
●
FB-16 is used to set the door open limit delay in the case of manual door. This parameter is valid
when the manual door function is used.
●
FB-17 is used to set the holding time before forced door close is implemented.
If the forced door close function is enabled, the system enters the forced door close state and
sends a forced door close signal when there is no door close signal after the time set in this
parameter is reached.
8.15 Protection Function Parameters
8.15.1 Motor Overload Protection
Function Code Parameter Name Setting Range Default Unit Property
FC-01
Program control 2 for protection
function
Bit0: Overload
protection
1 -
★
FC-02
Overload protection coefcient 0.50–10.00 1.00 -
★
FC-03
Overload pre-warning coefcient 50–100 80 %
★
FC-01 Bit0 = 0: overload protection disabled; BIT0 = 1: overload protection enabled
For details on the description and setting method of FC-01, see section 8.21.1.
After detecting that the output current exceeds (FC-02 x Rated motor current) and the duration lasts the
time specied in the inverse time lag curve, the controller outputs fault Err11 indicating motor overload.
After detecting that the output current exceeds (FC-03 x Rated motor current) and the duration lasts the
time specied in the inverse time lag curve, the controller outputs a pre-warning signal.
8.15.2 Controller Protection
Function Code Parameter Name Setting Range Default Unit Property
FC-00
Program control for
protection function
Bit0: Short circuit to ground detection
at power-on
0 -
★
FC-01
Program control 2 for
protection function
Bit0: Canceling protection at output
phase loss, Canceling protection at
input phase loss
0 -
★
1. Short circuit to ground detection at power-on
● FC-00 Bit0 = 1: The controller detects the short circuit to ground fault at power-on. If detecting
the fault, the controller blocks the output immediately and reports the fault.