User Manual 8 Description of Function Codes
- 245 -
times reach the value set in Fb-09, the system reports fault Err48.
●
FB-07 is used to set the arrival gong output delay.
When the value of this parameter is larger than 10 and the car display is switched over to the
destination oor, the system outputs the arrival gong after the time set in this parameter. If the
value is smaller than 10, the system outputs the arrival gong at stop.
●
FB-08 is used to set the door close protection time.
After outputting the door close command, if the system does not receive the door close limit
signal after the time set in this parameter, the system re-closes the door. When the door open/
close times reach the value set in Fb-09, the system reports fault Err49.
8.14.3 Door Re-open Times and Door State at Standby
Function Code Parameter Name Setting Range Default Unit Property
Fb-09
Door open/close protection times 0–20 0 -
☆
Fb-10
Door state of standby elevator 0–2 0 -
☆
●
Fb-09 is used to set the door re-open/re-close times allowed when door open/close is abnormal.
●
Fb-10 is used to set the door state when the elevator is in stop and standby state.
The values are as follows:
● 0: Closing the door as normal at base oor
● 1: Waiting with door open at base oor
● 2: Waiting with door open at each oor
8.14.4 Door Open Holding Time
Function Code Parameter Name Setting Range Default Unit Property
Fb-11
Door open holding time for hall call 1–1000 5 s
☆
Fb-12
Door open holding time for car call 1–1000 3 s
☆
Fb-13
Door open holding time at base oor 1–1000 10 s
☆
Fb-14
Door open holding time at such signal input 10–1000 30 s
☆
Fb-11 is used to set the door open holding time when there is a hall call. The elevator closes the door
immediately after receiving a door close command.
Fb-12 is used to set the door open holding time when there is a car call. The elevator closes the door
immediately after receiving a door close command.
Fb-13 is used to set the door open holding time after the elevator arrives at the base oor. The elevator
closes the door immediately after receiving a door close command.
Fb-14 is used to set the door open holding time when there is door open delay input. The elevator closes
the door immediately after receiving a door close command.