User Manual 11 Inspection and Mainetenance
- 293 -
11
need not be performed again because it has been completed before delivery.
The measured insulating resistance must be greater than 5 MΩ.
Figure 11-1 Main circuit insulation test
R S
T
U
V
W
PB
+
-
500 VDC
megametor
+
-
NICE3000
new
11.3 Replacement of Vulnerable Components
11.3.1 Cooling Fan
Component Possible Cause Judging Criteria
Cooking fan
Bearing worn
Blade aging
Whether there is crack on the blade
Whether there is abnormal vibration noise upon startup
Removing and Installing the Cooling Fan of a Plastic Housing
Removing the cooling fan
Depress the hooks on the fan cover, and pull upward to
remove the fan cover.
Hooks
Lift the fan a little, disconnect the fan power cables
from the socket, and then remove the fan.