8 Description of Function Codes NICE3000
new
User Manual
- 250 -
Function Code Parameter Name Setting Range Default Unit Property
Fd-09
HCB:JP1 output
0: Invalid
1: Up arrival indicator
2: Down arrival indicator
3: Fault output
4: Non-door zone stop output
5: Non-service state output
6: Door close button indicator
output
1 -
★
Fd-10
HCB:JP2 output 2 -
★
These parameters are used to set the functions of pins 1 and 4 of JP1 and JP2 on the HCB.
The setting is effective to the HCBs for all oors.
8.17.3 HCB-B Terminal Function Selection
Function Code Parameter Name Setting Range Default Unit Property
Fd-11
HCB-B:JP1 input
0: Reserved
NO/NC input:
1/33: Light-load signal
2/34: Half-load signal
3/35: Door 2 selection
4/36: Door 2 restricted (back
door forbidden)
5/37: Door 1 safety edge
6/38: Door 2 safety edge
7/39: Single/Double door
selection
0 -
★
Fd-12
HCB-B:JP2 input 0 -
★
Fd-13
HCB-B:JP3 input 0 -
★
Fd-14
HCB-B:JP4 input 0 -
★
Fd-15
HCB-B:JP5 input 0 -
★
Fd-16
HCB-B:JP6 input 0 -
★
These parameters are used to set the functions of pins 2 and 3 of JP1 to JP6 on the HCB-B no-display
parallel-serial conversion board.
The setting is effective to all HCB-Bs connected to the system.
Function Code Parameter Name Setting Range Default Unit Property
Fd-17
HCB-B:A1 output
0: Reserved
1: Fault output
2: Non-door zone stop output
3: Non-service state output
4: Fire emergency output
5: Power failure emergency
output
6: Door lock valid
7: Night output signal
0 -
★
Fd-18
HCB-B:A2 output 0 -
★
Fd-19
HCB-B:B1 output 0 -
★
Fd-20
HCB-B:B2 output 0 -
★
Fd-21
HCB-B:C1 output 0 -
★
Fd-22
HCB-B:C2 output 0 -
★
Fd-23
HCB-B:C3 output 0 -
★
Fd-24
HCB-B:C4 output 0 -
★
Fd-25
HCB-B:C5 output 0 -
★
Fd-26
HCB-B:C6 output 0 -
★