8 Description of Function Codes NICE3000
new
User Manual
- 222 -
11/43 active), the elevator will not open or close the door automatically. You need to open or close the
door by jog operation (optional) implemented on the door open or close button. In this state, the elevator
responds only to car calls, and only one car call can be registered each time.
Other re emergency-related functions are set in F6-44.
Function Code Parameter Name Setting Range Default Unit Property
F6-44
Fire emergency function selection 0–65535 16456 -
★
F6-44 is used to select the re emergency-related functions. Each bit of the function code denes a
function, as described in the following table.
If a bit is set to 1, the function indicated by this bit is enabled; if this bit is set to 0, the function is disabled.
For details on how to view and set this function code, see the descriptions in section 8.21.1.
The functions dened by the binary bits of F6-44 are described in the following table.
Bit Function Description Default
Bit0 to Bit2 Reserved - 0
Bit3
Arrival gong output in
inspection or re emergency
state
The arrival gong is output in the inspection or re
emergency state.
0
Bit4
Multiple car calls registered
in re emergency state
Multiple car calls can be registered in the re emergency
state. If this function is disabled, only one car call can be
registered.
0
Bit5
Retentive at power failure in
re emergency state
In the re emergency state, the current system and car
state will be memorized at power failure and be resumed
after the system is powered on again.
0
Bit6
Closing door by holding
down the door close button
In the re emergency state, the door close process can
be completed only by holding down the door close button
until the door close limit is reached. Otherwise, it will be
switched over to door open automatically.
0
Bit7 Reserved - 0
Bit8
Door close at car call
registering
The elevator enters the door close process automatically if
a car call is registered.
0
Bit9
Displaying hall calls in re
emergency state
Hall calls are displayed in the re emergency state. 0
Bit10 Fireghter forced running
JP22 is used for reghter forced running input.
In the reghter running state, when the JP22 input switch
and the door close button are enabled simultaneously,
the buzzer tweets and the system outputs the door close
signal. If the door lock is not enabled within 10s, the system
outputs the shorting door lock circuit contactor signal, and
the elevator starts running (used together with SCB-A).
0
Bit11
Exiting reghter state upon
arrival at re emergency
oor
The system can exit the reghter state only after the
elevator arrives at the re emergency oor.
0
Bit12
Not clearing car calls
at reverse door open in
reghter running state
In the reghter running state, the car calls that have been
registered are not cleared at reverse door open.
0
Bit13 Reserved - 0