8 Description of Function Codes NICE3000
new
User Manual
- 228 -
Function Code Parameter Name Setting Range Default Unit Property
F9-01
Time for fan and lamp to be turned off 0–240 2 min
☆
It is used to set the time that fan and lamp stays ON before being turned off automatically.
If there is no running command in the automatic running state, the system turns off the fan and lamp
automatically after the time set in this parameter.
Function Code Parameter Name Setting Range Default Unit Property
F9-02
Motor running time limit 0–45 45 s
★
It is used to set the running time limit of the motor.
In normal running state, if the continuous motor running time in the same direction between two adjacent
oors exceeds the setting of this parameter but no leveling signal is received, the system will perform
protection.
This parameter is mainly used for over-time protection in the case of steel rope slipping on the traction
sheave.
If this parameter is set to a value smaller than 3s, it becomes invalid.
Function Code Parameter Name Setting Range Default Unit Property
F9-03
Clock: year 2000–2100 Current year YYYY
☆
F9-04
Clock: month 1–12 Current month MM
☆
F9-05
Clock: day 1–31 Current day DD
☆
F9-06
Clock: hour 0–23 Current hour HH
☆
F9-07
Clock: minute 0–59 Current minute
MM
☆
These parameters are used to set the current date and time of the system.
Time keeping is supported at power failure. You need to set the current system time correctly so that
functions related to the time can be implemented.
Function Code Parameter Name Setting Range Default Unit Property
F9-09
Accumulative running time 0–65535 0 h
●
F9-11
High byte of running times 0–9999 0 -
●
F9-12
Low byte or running times 0–9999 0 -
●
These parameters are used to view the actual accumulative running time and running times of the elevator.
Running times of the elevator = F9-11 x 10000 + F9-12.
Function Code Parameter Name Setting Range Default Unit Property
F9-13
Maintenance notication period 0–99 0 day
★
It is the forced maintenance notication function. When this parameter is set to a non-zero value, this
function is enabled, and the system starts to count the days. If there is no power-off operation during the
counting and the counted days reaches the value of this parameter, the elevator enters the parking state
and the system reports Err08, notifying that the elevator must be maintained and cannot run. Maintenance
personnel need to power off and maintain the elevator, and then the system clears the value to 0 and