Current Transformer
4 - 23
Measurements
Note: The VDC voltage is limited to 10 V. If n/a appears in the VDC box,
decrease the test current to lower the voltage generated at the transformer’s
secondary winding below 10 V.
IDC: actual test current from 6A DC output or 400A DC output
VDC: voltage that IDC generates at the transformer’s secondary
winding, measured at V DC input
R meas: transformer’s winding resistance, calculated from VDC / IDC
Time: total elapsed test time
Dev: deviation in % between the maximum and the minimum
measured values evaluated within the last 10 seconds of the
measurement. The results are considered stable if Dev < 0.1%.