Technical Data
16 - 15
Outputs on the CPC 100 Front Panel
6A / 130V AC output
While using the 6A / 130V AC output, disconnect any cables that may be
plugged in to any of the high-current outputs (800A AC or 400A DC), or to the
6A DC output.
Table 8:
Technical data of
6A / 130V AC output -
all ranges
Note: The outputs of the CPC 100 front panel are not controlled.
Furthermore, there is no internal measurement provided. To measure
a front panel output signal, connect it to a measuring input:
current measurement: to IAC/DC input
voltage measurement: to V1AC or VDC input
6A / 130V AC output - all ranges
Connection 4mm banana sockets
Insulation The 6A/130V AC output is internally connected with
the 6A DC output. Apart from this, the output is
insulated against all other inputs and outputs.
Voltage with reference to earth must not exceed
200Vrms and 280V peak on either socket.
Reinforced insulation against mains power supply, all
interfaces and other safety low-voltage circuits.
Measurement No internal measurement provided. To measure this
output signal, connect it to a measuring input:
current measurement: at IAC/DC input
voltage measurement: at V1AC input