CPC 100 V1.41
16 - 26
Resolution Measurement Display
3V: 150 μV/bit
300mV: 30 μV/bit
30mV: 3 μV/bit 10 μV
Note: When using the CTRogowski test card, the 3V V2AC input uses an
additional software-based integration method.
In the range of 50Hz < f < 60Hz, this results in a phase shift of 90° as
well as an additional phase error of +/- 0.1° and an additional
amplitude error of +/- 0.01%.
For frequencies in the range of 15Hz < f < 400Hz, the phase error is
not specified, and the amplitude error can be up to +/- 0.50% higher.
3V V2AC input