EasyManua.ls Logo

Panasonic fp2/fp2sh - Page 280

Panasonic fp2/fp2sh
374 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11-12
FP2/FP2SH/FP10SH
Item
Add-
ress
Name
Default
value
Descriptions
Time
setting
for
FP2SH/
FP10SH
29
Operation time setting for
communication
processing
240 µs
0 to 52428 µs
If the response of the connected
programmable display is show, please
make the value bigger.
30
Time-out time setting of
system watching dog
timer
100 ms 0.4 to 640 ms
31
Multi-frame
communication time
settings in the computer
link and communication
time setting for data
sending buffer
6500 ms 10 to 81917.5 ms
32
Time-out time setting for
the F145 (SEND)/P145
(PSEND), F146
(RECV)/P146 (PRECV),
F152 (RMRD)/P152
(PRMRD) and F153
(RMWT)/P153 (PRMWT)
instructions
10000 ms 10 to 81917.5 ms
33
Effective time setting for
monitoring
163837.5
ms
2500 to 163837.5 ms
34
Constant scan time
setting
0 ms:
Normal
scan
0 to 640 ms:
Scans once each specified time
interval.
Set “0”: Normal scan
Setting time can be obtained using the
formula
Set time= Set valuex 0.1 (ms)
Time
setting
for FP2
31
Multi-frame
communication time
settings in the computer
link
6500 ms 10.0 to 8190.0 ms
32
Time-out time setting for
the F145 (SEND)/P145
(PSEND), F146
(RECV)/P146 (PRECV),
F152 (RMRD)/P152
(PRMRD) and F153
(RMWT)/P153 (PRMWT)
instructions
2000 ms 10.0 to 8190.0 ms
33
Program block-editing
time in the RUN mode
10000 µs 800.0 to 52428.0 µs
34
Constant scan time
setting
0 :
Normal
scan
0 to 640 ms:
Scans once each specified time
interval.
Set “0”: Normal scan

Table of Contents