11-12
FP2/FP2SH/FP10SH
Item
Add-
ress
Name
Default
value
Descriptions
Time
setting
for
FP2SH/
FP10SH
29
Operation time setting for
communication
processing
240 µs
0 to 52428 µs
If the response of the connected
programmable display is show, please
make the value bigger.
30
Time-out time setting of
system watching dog
timer
100 ms 0.4 to 640 ms
31
Multi-frame
communication time
settings in the computer
link and communication
time setting for data
sending buffer
6500 ms 10 to 81917.5 ms
32
Time-out time setting for
the F145 (SEND)/P145
(PSEND), F146
(RECV)/P146 (PRECV),
F152 (RMRD)/P152
(PRMRD) and F153
(RMWT)/P153 (PRMWT)
instructions
10000 ms 10 to 81917.5 ms
33
Effective time setting for
monitoring
163837.5
ms
2500 to 163837.5 ms
34
Constant scan time
setting
0 ms:
Normal
scan
0 to 640 ms:
Scans once each specified time
interval.
Set “0”: Normal scan
Setting time can be obtained using the
formula
Set time= Set valuex 0.1 (ms)
Time
setting
for FP2
31
Multi-frame
communication time
settings in the computer
link
6500 ms 10.0 to 8190.0 ms
32
Time-out time setting for
the F145 (SEND)/P145
(PSEND), F146
(RECV)/P146 (PRECV),
F152 (RMRD)/P152
(PRMRD) and F153
(RMWT)/P153 (PRMWT)
instructions
2000 ms 10.0 to 8190.0 ms
33
Program block-editing
time in the RUN mode
10000 µs 800.0 to 52428.0 µs
34
Constant scan time
setting
0 :
Normal
scan
0 to 640 ms:
Scans once each specified time
interval.
Set “0”: Normal scan