Parts and FunctionsFP2/FP2SH
2 − 37
2.9 Input Units Specifications
2.9.3 64-point Type DC Input Unit
Specifications
Item Description
Part number FP2−X64D2
Insulation method Optical coupler
Rated input voltage 24V DC
Rated input current Approx. 4.3mA (at 24V DC)
Input impedance Approx. 5.6kΩ
Input voltage range 20.4 to 26.4V DC
Min. on voltage/Min. on current 19.2V/4mA
Max. off voltage/Max. off current 5.0V/1.5mA
Response time off → on 0.2ms or less
on → off 0.3ms or less
Internal current consumption (at 5V DC) 100mA or less
Common method (Input points per common) 32 points/common
Either the positive or negative of the input power supply can be
connected to common terminal.
Operating indicator 32-dot LED display (lit when on, switching)
External connection method Connectors (MIL type two 40-pin)
Weight Approx. 120g
Note
Keep the number of input points per common which are simulta-
neously on within the following range as determined by the input
voltage and ambient temperature.
50/
127.4
55/
131
Number of
points per
common which
are simulta-
neous on
Ambient temperature (°C/°F)
24V DC