11-40 
FP2/FP2SH/FP10SH/FP3  (A: Available, N/A: Not available) 
Name  Descriptions 
Read-
ing 
Writ-
ing 
FP3 
FP2/ 
FP2SH 
DT9132 
DT9133 
DT90132 
DT90133 
MEWNET-F 
(remote I/O) error 
slave station 
number – current 
condition  
(when DT9131/ 
DT90131 is H0, 
H1, H2 or H3) 
The bit corresponding to the station 
number of the MEWNET-F where an 
error is occurring is set to on. Monitor 
using binary display. 
 
(1: Error slave station, 0: Normal slave 
station) 
A  N/A 
MEWNET-F 
(remote I/O) I/O 
verify error slave 
station number  
(when DT9131/ 
DT90131 is H100, 
H101, H102 or 
H103) 
When the installed condition of a 
MEWNET-F slave station set unit has 
changed since the power was turned 
on, the bit corresponding to that slave 
station number will be set to on. 
Monitor using binary display. 
 
(1: Error slave station, 0: Normal slave 
station) 
DT9134 
DT9135 
DT90134 
DT90135 
MEWNET-F 
(remote I/O) error 
slave station 
number – record  
(when DT9131/ 
DT90131 is H0, 
H1, H2 or H3) 
The bit corresponding to the slave 
station number of the MEWNET-F 
where an error is occurring will be set 
to on. Monitor using binary display. 
 
(1: Error slave station, 0: Normal slave 
station) 
MEWNET-F 
(remote I/O) 
momentary 
voltage drop slave 
station number  
(when DT9131/ 
DT90131 is H100, 
H101, H102 or 
H103) 
If a momentary voltage drop at 
MEWNET-F slave station set, the bit 
corresponding to that slave station 
number will be set to on. Monitor using 
binary display. 
 
(1: Error slave station, 0: Normal slave 
station)