11-40
FP2/FP2SH/FP10SH/FP3 (A: Available, N/A: Not available)
Address
Name Descriptions
Read-
ing
Writ-
ing
FP3
FP2/
FP2SH
FP10SH
DT9132
DT9133
DT90132
DT90133
MEWNET-F
(remote I/O) error
slave station
number current
condition
(when DT9131/
DT90131 is H0,
H1, H2 or H3)
The bit corresponding to the station
number of the MEWNET-F where an
error is occurring is set to on. Monitor
using binary display.
(1: Error slave station, 0: Normal slave
station)
A N/A
MEWNET-F
(remote I/O) I/O
verify error slave
station number
(when DT9131/
DT90131 is H100,
H101, H102 or
H103)
When the installed condition of a
MEWNET-F slave station set unit has
changed since the power was turned
on, the bit corresponding to that slave
station number will be set to on.
Monitor using binary display.
(1: Error slave station, 0: Normal slave
station)
DT9134
DT9135
DT90134
DT90135
MEWNET-F
(remote I/O) error
slave station
number record
(when DT9131/
DT90131 is H0,
H1, H2 or H3)
The bit corresponding to the slave
station number of the MEWNET-F
where an error is occurring will be set
to on. Monitor using binary display.
(1: Error slave station, 0: Normal slave
station)
MEWNET-F
(remote I/O)
momentary
voltage drop slave
station number
(when DT9131/
DT90131 is H100,
H101, H102 or
H103)
If a momentary voltage drop at
MEWNET-F slave station set, the bit
corresponding to that slave station
number will be set to on. Monitor using
binary display.
(1: Error slave station, 0: Normal slave
station)