Parts and FunctionsFP2/FP2SH
2 9
2.2 FP2 CPU
Status Indicator LEDs
These LEDs display the current mode of operatin or the occurrence of error.
LED
Description
LED
D
escr
i
pt
i
on
RUN (green) This lights in the RUN mode, to indicate that the program is being executed.
It flashes during forced input/output.
PROG. (green)
This lights in the PROG. mode. Operation stops while this LED is lighted.
It flashes when waiting for connection of slave station on remote I/O system.
If the memory is initialized, the brightness dims, indicating that initialization is being
executed.
TEST (green) This lights in the test operation mode.
BREAK (green) This lights in the operation halts at a break during a test run or halts during the step
operation mode for the test run.
ERROR (red) This lights if an error is detected during the self-diagnostic function.
BATT. (red) This lights when the voltage of the backup battery drops below a specific value.
ALARM (red) This lights if a hardware error occurs, or if operation slows because of the program,
and the watchdog timer is activated.
Initialize/Test Switch
This switch clears errors, initializes the operation memory and sets the test operation
mode.
Switch
position
Operation
mode
S
w
i
tc
h
pos
i
t
i
on
O
perat
i
on mo
d
e
INITIALIZE (upward)
In the PROG. mode:
The contents of the operation memory are initialized. However, the system register
(including the I/O map) and the program are not initialized. If the error of self-diag-
nostic error code 42 or lower is occured, the special internal relays R9000 to R9008
and the special data register DT90000 are not cleared.
In the RUN mode:
Operation errors, remote I/O system errors, and battery errors are cleared.
(center) The switch should normally be left in this position.
TEST
(downward)
Setting this switch to the downward position in the PROG. mode, accesses the test
mode. Switching to the RUN mode in this state, initiates test operation.
To return from the test mode to the normal operation, return this switch to the center
position in the PROG. mode.
Note
By turning on the initialize/test switch while in the PROG.mode,
you can be specify the type of operation memory to be cleared
with system register 4.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic fp2/fp2sh and is the answer not in the manual?

Panasonic fp2/fp2sh Specifications

General IconGeneral
BrandPanasonic
Modelfp2/fp2sh
CategoryController
LanguageEnglish

Related product manuals