452 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Chapter 11 Troubleshooting
Blocked Start
1. The number of starts count within the
past hour period equals the value set in the
Starts Per Hour (Parameter 205)
1. Check Time to Start (Parameter 31) and wait that
amount of time, or change the configuration to
allow more starts/hour.
2. The time expired since the most recent
start is less than the value set in the Starts
Interval (Parameter 206)
2. Check Time to Start (Parameter 31) and wait that
amount of time, or change the configuration to
shorten the interval between starts.
Trip Description Possible Cause Corrective Action