EasyManua.ls Logo

Rockwell Automation Allen-Bradley E300

Rockwell Automation Allen-Bradley E300
546 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 471
Parameter List Appendix B
Trip/Warn History
(continued)
148 WarnHistoryMaskC
C.History.PTCWarningEn
C.History.ModuleMismatchWarningEn
C.History.ExpansionBusWarningEn
C.History.NumberOfStartsWarningEn
C.History.OperatingHoursWarningEn
Warning History
Mask for Control-
based Warnings
UINT 2 1 Bit0= Reserved
Bit1= PTCWarning
Bit2= DLXWarning
Bit3= Reserved
Bit4= Reserved
Bit5= Reserved
Bit6= Reserved
Bit7= ConfigWarning
Bit8= OptionMatchWarn
Bit9= DLXFBTimeoutWarn
Bit10= ExpansionBusWarn
Bit11= PMNumberOfStarts
Bit12= PMOperatingHours
0x1FFF
149 WarnHistoryMaskA C.History.Analog1Ch00WarningEn
C.History.Analog1Ch01WarningEn
C.History.Analog1Ch02WarningEn
C.History.Analog2Ch00WarningEn
C.History.Analog2Ch01WarningEn
C.History.Analog2Ch02WarningEn
C.History.Analog3Ch00WarningEn
C.History.Analog3Ch01WarningEn
C.History.Analog3Ch02WarningEn
C.History.Analog4Ch00WarningEn
C.History.Analog4Ch01WarningEn
C.History.Analog4Ch02WarningEn
Warning History
Mask for Analog
Input Based
Warnings
UINT 2 1 Bit0= InAnMod1Ch00Warn
Bit1= InAnMod1Ch01Warn
Bit2= InAnMod1Ch02Warn
Bit3= InAnMod2Ch00Warn
Bit4= InAnMod2Ch01Warn
Bit5= InAnMod2Ch02Warn
Bit6= InAnMod3Ch00Warn
Bit7= InAnMod3Ch01Warn
Bit8= InAnMod3Ch02Warn
Bit9= InAnMod4Ch00Warn
Bit10= InAnMod4Ch01Warn
Bit11= InAnMod4Ch02Warn
0xFFF
150 Reserved
Trip Snapshot
151 TSL1Current Snapshot of the
actual L1 Phase
Current at trip
DINT 4 100 0 2000000000 0 Amps
152 TSL2Current Snapshot of the
actual L2 Phase
Current at trip
DINT 4 100 0 2000000000 0 Amps
153 TSL3Current Snapshot of the
actual L3 Phase
Current at trip
DINT 4 100 0 2000000000 0 Amps
154 TSThermUtilized Snapshot of %
Thermal Capacity
Used at trip
UINT 2 1 0 100 0 %
155 TSGFCurrent Snapshot of the
Ground Fault
Current at trip
INT 2 100 0 2540 0 Amps
156 TSL1toL2Voltage Snapshot of 3
Phase RMS Voltage
Line-Line at trip
UINT 2 10 0 65535 0 Volt
157 TSL2toL3Voltage Snapshot of 3
Phase RMS Voltage
Line-Line at trip
UINT 2 10 0 65535 0 Volt
158 TSL3toL1Voltage Snapshot of 3
Phase RMS Voltage
Line-Line at trip
UINT 2 10 0 65535 0 Volt
159 TSTotalRealPwr Snapshot of Total
Real Power at trip
DINT 4 1000 -2000000000 2000000000 0 kW
160 TSTotalkVAR Snapshot of Total
Reactive Power at
trip
DINT 4 1000 -2000000000 2000000000 0 kVAR
161 TSTotalkVA Snapshot of Total
Apparent Power at
trip
DINT 4 1000 0 2000000000 0 kVA
162 TSTotalPF Snapshot of Total
True Power Factor
(PF) at trip
INT 2 10 -1000 1000 0 %
Group
Param
No.
Parameter Name Device Profile Tag Name Description Type
Data Size
(bytes)
Scale
Factor
Min Max Default Units

Table of Contents