EasyManua.ls Logo

Rockwell Automation Allen-Bradley E300

Rockwell Automation Allen-Bradley E300
546 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 97
System Operation and Configuration Chapter 4
Table 76 - Analog Module 1 – Input Channel 00 RTD Type Enable (Parameter 442)
Analog Module 1 – Input Channel 01 Type
Analog Module 1 – Input Channel 01 Type (Parameter 446) defines the type of
analog signal that Input Channel 01 of Analog Module 1 will be monitoring.
Table 77 - Analog Module 1 – Input Channel 01 Type (Parameter 446)
Analog Module 1 – Input Channel 01 Format
Analog Module 1 – Input Channel 01 Format (Parameter 447) defines the data
format for howthe analog reading is reported.
Table 78 - Analog Module 1 – Input Channel 01 Format (Parameter 447)
AnalogModule1InputChannel01TemperatureUnit
Value Assignment Description
0 3-Wire Scan a 3-wire RTD sensor
1 2-Wire Scan a 2-wire RTD sensor
Value Assignment Description
0 Disabled Disable the analog input
1 4To20mA Read an analog current signal from 4…20 mA
2 0To20mA Read an analog current signal from 0…20 mA
3 0To10Volts Read an analog voltage signal from 0…10 V DC
4 1To5Volts Read an analog voltage signal from 1…5 V DC
5 0To5Volts Read an analog voltage signal from 0…5 V DC
6 100Pt385 Read a 100 Ω Pt 385 RTD Sensor
7 200Pt385 Read a 200 Ω Pt 385 RTD Sensor
8 500Pt385 Read a 500 Ω Pt 385 RTD Sensor
9 1000Pt385 Read a 1000 Ω Pt 385 RTD Sensor
10 100Pt3916 Read a 100 Ω Pt 3916 RTD Sensor
11 200Pt3916 Read a 200 Ω Pt 3916 RTD Sensor
12 500Pt3916 Read a 500 Ω Pt 3916 RTD Sensor
13 1000Pt3916 Read a 1000 Ω Pt 3916 RTD Sensor
14 10Cu426 Read a 10 Ω Cu 426 RTD Sensor
15 100Ni618 Read a 100 Ω Ni 618 RTD Sensor
16 120Ni672 Read a 120 Ω Ni 672 RTD Sensor
17 604NiFe518 Read a 604Ω NiFe 518 RTD Sensor
18 150ohm Read a resistance signal from 0…150 Ω
19 750ohm Read a resistance signal from 0…750 Ω
20 3000ohm Read a resistance signal from 0…3000 Ω
21 6000ohm
Read a resistance signal from 0…6000 Ω. This
setting can be used with PTC and NTC sensors.
Value Assignment Description
0 EngUnits Engineering Units (mA, V, °C, °F, or Ω)
1 EngUnitsTimes10 Engineering Units x 10 (mA, V, °C, °F, or Ω)
2 RawProportional Raw / Proportional (-32768…+32767)
3 ScaledForPID Scaled for PID (0…16383)

Table of Contents