PIN Designation Function
11 Uni-I 13 Universal input 13, configurable:
•
S
tatic control input G1
•
Universal input: resetting (OSSD pair 3), sleep mode, restarting
the device, pausing event recording
12 Uni-I 14 Universal input 14, configurable:
•
Static control input G2
•
Universal input: EDM (external device monitoring, OSSD pair 3),
sleep mode, restarting the device, pausing event recording
13 Uni-I 15 Universal input 15, configurable:
•
Static control input H1
•
Universal input: resetting (OSSD pair 4), sleep mode, restarting
the device, pausing event recording
14 Uni-I 16 Universal input 16, configurable:
•
Static control input H2
•
Universal input: EDM (external device monitoring, OSSD pair 4),
sleep mode, restarting the device, pausing event recording
15 Uni-O 03 Universal output 3: contamination, fault, reset required (OSSD pair
3), monit
oring result
16 Uni-O 04 Universal output 4: contamination, fault, reset required (OSSD pair
4), monitoring result
17 0 V DC Voltage for inputs and outputs (0 V DC)
1)
1)
If at least one connection of the female connector XG2 is used, this 0 V connection must be connected in
the control cabinet to 0 V DC of the power supply unit using a low-impedance and star-point connection.