Monitoring functions
SIMOCODE pro
5-10 GWA 4NEB 631 6050-22 DS 03
Response at warning level
Here you can set how SIMOCODE pro should respond if the warning level is
undershot:
See also "Tables of responses of SIMOCODE pro" in Chapter "Important
information".
Table 5-8: "Warning level" response for voltage monitoring
Hysteresis for voltage, cos phi, power
Here you can set the hysteresis for voltage, cos phi and power.
Response Warning level
Deactivated X
Signaling X
Warning X
Tripping -
Delay 0 - 25.5 s (0.5 s
)
Hysteresis for voltage, cos phi, power 0 to 15% of the threshold value
in 1% increments (5%
)